Tags are declared in TOML files under a project's tags/ folder — any structure, loaded recursively. Each entry names a point, types it, binds it to a device address, and optionally opts into history.

Format

A tag file.

# projects/press-line/tags/hydraulics.toml
[[tags]]
name = "HeadPressure"
path = "press/hydraulics/HeadPressure"
data_type = "f32"
device = "press-plc"
address = "DB2.DBD26"
scan_group = "fast"
description = "Hydraulic head pressure at the platen"
eng_units = "psi"
history = { enabled = true, deadband_mode = "absolute", deadband_value = 0.5 }

[[tags]]
name = "PumpRunning"
path = "press/hydraulics/PumpRunning"
data_type = "bool"
device = "press-plc"
address = "DB1.DBX0.0"
scan_group = "normal"
Fields

Field reference.

Field
Default
Description
name
required
Display name.
path
required
Slash-delimited path, unique within the project. Screens and the API address tags by it.
data_type
required
bool, i16, u16, i32, i64, f32, f64, or string.
device
—
A [[devices]] name from server.toml. Omit for a memory tag the gateway holds itself.
address
—
Driver-specific point address — grammar below.
scan_group
"default"
Scan-group label. OPC UA applies its configured interval; other adapters retain their device-level cadence.
description
—
Human-readable description.
eng_units
—
Engineering-unit metadata on the tag definition, e.g. psi, degC, or RPM. Not included in live TagValue payloads.
kind
"control"
"control" or "config" — classifies the tag for write auditing.
history
—
Per-tag historian settings — table below.

Tag paths are per-project — two projects can both define plant/Temperature. Within one project a duplicate path (even across files) is rejected at publish.

Types

Data types.

bool, i16, u16, i32, i64, f32, f64, string. Choose a type supported by the adapter's conversion rules. Supported conversions can widen or narrow values; unsupported combinations can produce null or bad readings. For example: a BACnet Binary object's present-value is an enumerated 0/1 on the wire, so declare it i16, not bool.

Addressing

Address grammar by driver.

Driver
Grammar
Examples
S7
DB<n>.DB<X|B|W|D><offset>[.<bit>][,S<N>|,WS<N>]
DB1.DBX0.0 · DB2.DBD26 · DB8.DBB54,S20. Also I/E (inputs), Q/A (outputs), M (markers): I0.0, IW4, QD8, MB2; T5 and C10. S<N>: STRING, 2+N bytes; WS<N>: WSTRING, 4+2N bytes.
EtherNet/IP
Symbolic controller path
Motor.Speed · Program:MainProgram.Counter
Modbus TCP
<C|DI|HR|IR><0–65535>[:<type>]
C/DI default to bool; HR/IR to u16. Suffixes: bool, u16, i16, u32, i32, f32, u64, i64, f64, str<N>. C/DI accept bool. u64 has no SCADA tag conversion. HR100:f32 · HR300:str8.
OPC UA
NodeId string
ns=2;s=Tank_Level · ns=0;i=2258
MQTT
Broker topic
plant/line1/temperature
BACnet/IP
<object>,<0–4194303>[:<property>]
AI/AO/AV, BI/BO/BV, MSI/MSO/MSV, DEV; full names such as analog-value, or numeric types 0–1023. AV,1 · AI,2:units · BV,3 · 2,5:85. Property defaults to present-value.
sim
Pattern name
Sine_Wave · Square_Wave · Sawtooth

BACnet properties: present-value (pv), units, object-name, description, status-flags, reliability, out-of-service, priority-array, relinquish-default, event-state, object-identifier, device-type, location, object-list, object-type, vendor-identifier, vendor-name, protocol-services-supported, protocol-revision, property-list; numeric codes or property-<code> also work. Connection settings are on Devices & drivers.

Memory tags

Tags without a device.

Omit device and address and the gateway holds the value itself — useful for operator inputs, recipe staging, and inter-screen state. Memory tags are readable, writable, and historizable like any other tag.

[[tags]]
name = "TargetPressure"
path = "press/recipe/TargetPressure"
data_type = "f32"
eng_units = "psi"
[tags.history]

Per-tag history.

With the historian feature on and a PostgreSQL connection configured (see Server configuration), add a history block to each tag you want recorded. Tags without that block are not recorded. Aggregation is computed at query time — there are no rollup jobs to configure.

Field
Default
Description
enabled
true
Record this tag when the historian feature is on.
sample_mode
"on_change"
Uses on_change sampling; other configured values fall back to on_change.
sample_rate_ms
0
Minimum source-time interval between archived native samples. 0 disables time-based throttling; quality and deadband rules still apply.
deadband_mode
"none"
"none", "absolute", or "percent".
deadband_value
0.0
Change threshold below which samples are dropped.
[[tags]]
name = "OvenTemperature"
path = "oven/Temperature"
data_type = "f64"
device = "oven-plc"
address = "DB6.DBD8"

[tags.history]
enabled = true
sample_mode = "on_change"
sample_rate_ms = 1000   # throttle: at most one sample per second
deadband_mode = "absolute"
deadband_value = 0.5