Server configuration

View as Markdown

config/server.toml defines the gateway listener, features, logging, devices, scan groups, databases, authentication, and topology. Node settings and notifications use additional files.

Example

A server.toml with devices and history.

# config/server.toml
[server]
name = "plant-a"
bind_address = "0.0.0.0"
http_port = 8400

[features]
historian = true
hmi_serving = true

[logging]
level = "info"
format = "pretty"

[logging.file]
enabled = true
rotation = "daily"

[[scan_groups]]
name = "fast"
rate_ms = 100

[[scan_groups]]
name = "normal"
rate_ms = 250

[[devices]]
name = "s7-plc"
driver = "s7"
[devices.config]
host = "192.168.0.1"
rack = 0
slot = 1
poll_rate_ms = 500

[[databases]]
name = "historian"
driver = "postgresql"
[databases.config]
host = "localhost"
database = "thermite"
username = "thermite"
password_env = "THERMITE_DB_PASSWORD"
[server]

Identity and listener.

Field
Default
Description
name
required
Server instance name — shows in the admin dashboard and logs.
profile
"standard"
Gateway profile: "standard", "edge", "hub", "dmz-broker", or "arbiter". Accepted under the legacy key "role" too. Non-standard profiles are part of multi-gateway topologies (Commercial).
bind_address
"0.0.0.0"
HTTP bind address.
http_port
8400
HTTP port for the admin UI, project mounts, and APIs.
[features]

Subsystem switches.

Field
Default
Description
historian
true
Record tag history to PostgreSQL. Requires a [[databases]] entry.
hmi_serving
false
Serve HMI screens, thermite.js, and thermite.css.
transactions
true
Run transaction groups and named queries.
admin_dashboard
true
Serve the admin dashboard and its APIs on the gateway port.
[logging]

Console and file logging.

file.* keys live in a [logging.file] sub-table.

Field
Default
Description
level
"info"
"trace", "debug", "info", "warn", "error".
format
"pretty"
"pretty" for humans, "json" for log shippers.
buffer_size
2000
In-memory log buffer size (feeds the admin dashboard's log view).
file.enabled
true
Also write logs to the site's logs/ directory.
file.directory
"logs"
Log directory, relative to the site root.
file.rotation
"daily"
"daily", "hourly", or "never".
[[scan_groups]]

Named polling intervals for OPC UA tags.

OPC UA tags select an interval with scan_group = "<name>". S7, CIP, Modbus, and BACnet use the device's poll_rate_ms; the simulator uses update_rate_ms.

Field
Default
Description
name
required
Group name referenced by tags' scan_group field.
rate_ms
required
Poll interval in milliseconds. Minimum 10.
enabled
true
Disabled groups are ignored; their OPC UA tags use the device's default polling interval.
[[databases]]

PostgreSQL connections.

config.* keys live in a [databases.config] sub-table. An unbound historian needs one eligible PostgreSQL connection to bind; it does not choose between multiple candidates.

Field
Default
Description
name
required
Reference name — transaction groups and queries select databases by it.
driver
required
Use "postgresql".
enabled
true
Allow this connection to be used by the historian, transaction groups, and named queries.
config.host
"localhost"
Database hostname.
config.port
5432
Database port.
config.database
"thermite"
Database name.
config.username
"thermite"
Database user.
config.password
—
Plaintext password. Prefer password_env.
config.password_env
—
Name of an environment variable holding the password.
config.max_connections
5
Connection pool size (1–200).
Elsewhere

Config that lives on other pages.

[[devices]]

Per-driver connection settings for all seven drivers.

[auth]

Gateway users, sessions, and project-level roles.

[mesh] · [[peers]] · [redundancy]

Multi-gateway topologies — redundant pairs, hub-and-edge — are Commercial features configured with your deployment engineer.