Connect a BACnet controller

View as Markdown

Configure a BACnet/IP device, create typed tags, publish the project, and verify its readings. Screens subscribe to the same tag paths.

Scope

What the driver does — and its limits today.

  • Speaks BACnet/IP (UDP, default 47808): one ReadProperty per tag per poll, WriteProperty at an optional priority, typed values into the tag engine.
  • Unicast, by IP. You configure each controller's address — there is no Who-Is network scan.
  • No BBMD / foreign-device registration. Devices only reachable through a BACnet router (MS/TP trunks, other subnets behind a BBMD) aren't addressable through this driver.

Prerequisites: a configured Thermite site with the CLI on PATH and HMI serving enabled, a reachable BACnet/IP controller (or the device zoo's VAV farm), its IP, and the object type + instance of each point — a third-party BACnet browser helps you confirm the object list first.

01

Add the device.

# config/server.toml
[[devices]]
name = "ahu-1"                 # tags reference this via device = "ahu-1"
driver = "bacnet"
enabled = true

[devices.config]
host = "192.168.1.50"          # the controller's IP — required
port = 47808
poll_rate_ms = 1000
write_priority = 8             # optional: priority-array level for writes
02

Define the tags.

The address is <object>,<instance>[:<property>] — comma before the instance, optional colon-property (default present-value). From the site root, run thermite project init bacnet-demo, then add tags/ahu1.toml. History recording also requires the gateway historian and a PostgreSQL connection; see Server configuration for those settings.

# projects/bacnet-demo/tags/ahu1.toml
[[tags]]
name = "Space Temp"
path = "ahu1/space_temp"
data_type = "f32"              # Analog present-value is Real → f32
device = "ahu-1"
address = "AV,1"
eng_units = "degF"
history = { enabled = true }

[[tags]]
name = "Occupancy"
path = "ahu1/occupied"
data_type = "i16"              # Binary present-value is enumerated 0/1 → i16, NOT bool
device = "ahu-1"
address = "BV,3"

[[tags]]
name = "Fan Speed Cmd"
path = "ahu1/fan_speed_cmd"
data_type = "f32"
device = "ahu-1"
address = "AO,2"              # AnalogOutput 2 — writable at write_priority
Object (present-value)
Wire type
data_type
Analog — AI / AO / AV
Real
f32 (or f64)
Binary — BI / BO / BV
Enumerated 0/1
i16 (or i32 / u16) — not bool
MultiState — MSI / MSO / MSV
Unsigned
i16 (or i32 / u16)
:object-name, :description
CharacterString
string

Use a supported wire-type conversion. A bool tag on a Binary object reads null with bad quality. Writes carry the tag's declared type onto the wire; the driver is not object-aware: f32→Real, f64→Double, bool→Boolean, i16/i32/i64→SignedInt, u16→UnsignedInt — there is no Enumerated encoding. For an Analog output declare f32 so the write emits Real (not every device accepts Double for a Real present-value). Binary/MultiState writes are best-effort — an i16 emits SignedInt, which lenient controllers accept and strict ones may reject; test against your device.

03

Publish and verify.

Run the licensed or trial gateway with thermite-server --site . and publish the project. These curl examples use the default, disabled authentication; with authentication enabled, supply a session and the CSRF token for writes.

$ thermite project publish bacnet-demo
$ curl http://localhost:8400/p/bacnet-demo/api/tags/ahu1/space_temp
{ "type": "tag", "path": "ahu1/space_temp", "value": { "value": 71.4, "quality": "good", "timestamp": "2026-07-03T18:40:12.314Z" } }

# command the fan
$ curl -X PUT http://localhost:8400/p/bacnet-demo/api/tags/ahu1/fan_speed_cmd \
    -H "Content-Type: application/json" -d '{"value": 60.0}'

Check the device panel at http://localhost:8400/admin/ (or GET /api/devices). One UDP subtlety: BACnet/IP is connectionless, so a wrong host shows Connected initially. Transport failures change it to Reconnecting after the polling round; APDU timeouts and retries apply to each read. On a screen, bind the same paths with Thermite.subscribe("ahu1/space_temp", …) — see HMI screens.

Troubleshooting

The four failure shapes.

Device stuck Reconnecting, all tags bad

Transport failure. Wrong host/port, a firewall on UDP 47808, or the device is behind a BACnet router (unsupported). Confirm reachability with a BACnet browser from the same host.

Connected, but one tag bad-quality

Tag-level error. The object doesn't exist, the alias is wrong, or data_type doesn't match the wire type (bool on a Binary object → use i16).

A good reading is 0 or 1 where an analog value was expected

Check the object type: a Binary point returns 0/1. Unsupported wire-type/tag-type combinations produce null, bad-quality readings.

A write errors on Binary/MultiState

An i16 tag sends SignedInt; a u16 tag sends UnsignedInt. The driver does not emit Enumerated. Confirm the device's accepted write encoding.

On a read error the server log names the tag, object, and property; on a write failure, the tag and device. Use these details to find the misconfigured point.