Devices & drivers

View as Markdown

Devices are declared in config/server.toml: a [[devices]] entry names the connection, picks a driver, and passes driver-specific settings in [devices.config]. Tags bind to a device by name. Seven drivers ship in the runtime.

Shape

Every device entry looks the same.

[[devices]]
name = "press-plc"     # unique — tags reference this name
driver = "modbus"     # sim | s7 | cip | modbus | opcua | mqtt | bacnet
enabled = true       # connect at startup (default true)

[devices.config]     # driver-specific keys — tables below
host = "192.168.0.10"

How a tag names a point on each device — the address grammar — is covered per driver on Tags.

driver = "sim"

Simulated device

Generates read-only values without hardware. Tag addresses are patterns: Sine_Wave, Cosine_Wave, Triangle_Wave (f64), Square_Wave (bool), Sawtooth (i32), Random_Float (f64), Static_String (string). Use memory tags for writable gateway values.

Key
Default
Description
update_rate_ms
1000
Simulation update interval in ms (min 1).
[[devices]]
name = "sim-plc"
driver = "sim"
[devices.config]
update_rate_ms = 500
driver = "modbus"

Modbus TCP

Polls coils, discrete inputs, and holding/input registers over Modbus TCP.

Key
Default
Description
host
required
Device hostname or IP.
port
502
Modbus TCP port.
unit_id
255
Slave/unit ID (0–255).
poll_rate_ms
1000
Polling interval (min 10).
connect_timeout_secs
5
Connection timeout.
request_timeout_secs
3
Per-request timeout.
word_order
"big_endian"
"big_endian", "little_endian", "byte_swapped", or "word_swapped" — for multi-register values.
[[devices]]
name = "modbus-io"
driver = "modbus"
[devices.config]
host = "192.168.0.10"
unit_id = 1
poll_rate_ms = 250

Addressing
HR100, HR100:f32, IR50:i16, C0, HR300:str8 — register prefix plus optional type suffix.

driver = "s7"

Siemens S7

Reads and writes S7 data blocks over ISO-on-TCP (port 102).

Key
Default
Description
host
required
PLC hostname or IP.
port
102
ISO-on-TCP port; use 10102 for the hydraulic-press simulator's published host port.
rack
0
PLC rack number (0–7).
slot
1
PLC slot number (0–31).
poll_rate_ms
1000
Polling interval (min 10).
connect_timeout_secs
5
Connection timeout.
request_timeout_secs
5
Per-request timeout.
connection_type
"PG"
"PG", "OP", or "Basic".
[[devices]]
name = "s7-plc"
driver = "s7"
[devices.config]
host = "192.168.0.1"
rack = 0
slot = 1

Addressing
DB1.DBX0.0 (bit), DB2.DBD26 (f32/f64 at byte offset), DB8.DBB54,S20 (string).

driver = "cip"

EtherNet/IP (CIP)

Reads and writes controller tags by symbolic name — Allen-Bradley Logix-class controllers.

Key
Default
Description
host
required
Controller hostname or IP.
port
44818
CIP TCP port.
slot
0
CPU slot used for connected messaging; does not replace route_path.
route_path
—
Unconnected route as port,link pairs, e.g. "1,0" for backplane port 1, slot 0. Required when reaching the CPU through a separate Ethernet module.
poll_rate_ms
1000
Polling interval (min 10).
connect_timeout_secs
5
Connection timeout.
request_timeout_secs
10
Per-request timeout.
[[devices]]
name = "line-plc"
driver = "cip"
[devices.config]
host = "192.168.0.20"
slot = 0

Addressing
Symbolic controller paths: Motor.Speed, Tank_Level, Program:MainProgram.Counter.

driver = "opcua"

OPC UA

Polls and writes OPC UA server nodes. The integrated adapter uses security_mode = "none" and security_policy = "none"; it has no client certificate/key configuration for signed or encrypted sessions.

Key
Default
Description
endpoint_url
required
e.g. opc.tcp://host:4840.
poll_rate_ms
1000
Polling interval (min 10).
connect_timeout_secs
10
Connection timeout.
request_timeout_secs
30
Per-request timeout.
security_mode
"none"
Use "none" with this adapter; secure modes require client certificate material it does not configure.
security_policy
"none"
Use "none" with this adapter.
auth
"anonymous"
"anonymous" or "username".
username / password
— / ""
username is required when auth = "username"; password defaults to an empty string.
[[devices]]
name = "press-opcua"
driver = "opcua"
[devices.config]
endpoint_url = "opc.tcp://192.168.0.30:4840"
security_policy = "none"
security_mode = "none"

Addressing
NodeId strings: ns=2;s=Tank_Level or ns=0;i=2258.

driver = "mqtt"

MQTT

Subscribes to broker topics and maps payloads to tags. A tag's address is its topic; with the default json codec the payload is parsed as a JSON value matching the tag's data_type.

Key
Default
Description
url
required
mqtt://, mqtts://, ws://, or wss:// URL — the TLS schemes enable TLS defaults.
client_id
""
Client identifier presented to the broker.
username / password
—
Broker credentials, if required.
keep_alive_secs
60
MQTT keep-alive.
connect_timeout_secs
10
Connection timeout.
request_timeout_secs
10
Publish acknowledgment timeout.
clean_session
true
Start with a clean broker session.
max_inflight
64
Max unacknowledged messages.
qos
0
Subscription and publish QoS (0–2).
codec
"json"
Payload codec: "json" or "utf8".
protocol_version
"v3.1.1"
"v3.1.1", "v5", or "auto".
[[devices]]
name = "broker"
driver = "mqtt"
[devices.config]
url = "mqtt://192.168.0.5:1883"
client_id = "thermite-gw-01"
qos = 1

Addressing
The broker topic, e.g. plant/line1/temperature.

driver = "bacnet"

BACnet/IP

Reads and writes BACnet objects over BACnet/IP (UDP), addressing one controller directly by IP. Today the driver is unicast-to-a-known-IP: it does not run Who-Is discovery or register as a BBMD foreign device, so controllers behind a BACnet router (e.g. MS/TP segments) are not addressable through this adapter.

Key
Default
Description
host
required
Controller IP or hostname.
port
47808
BACnet/IP UDP port (0xBAC0).
poll_rate_ms
1000
Per-tag read cadence (min 10).
apdu_timeout_secs
3
Per-attempt APDU timeout.
apdu_retries
3
Retries after a timeout.
device_id
4194303
Local BACnet device instance the driver presents.
vendor_id
65535
Local vendor id in I-Am replies.
max_apdu_length
1476
One of 50, 128, 206, 480, 1024, 1476.
write_priority
—
Default write priority 1–16 for commandable objects; omit for none.
who_is_timeout_secs
3
Accepted in configuration; unused by the adapter's poll loop.
bacpypes3_segmentation_quirk
false
Compatibility workaround for bacpypes3 peers.
[[devices]]
name = "ahu-1"
driver = "bacnet"
[devices.config]
host = "192.168.1.50"
poll_rate_ms = 1000
write_priority = 8

Addressing
AV,1 · AI,2:units · BV,3 — object type, instance, optional property (defaults to present-value).

Behavior

Connection status and polling.

  • Drivers expose connection status and tag quality. Polling adapters publish bad quality on failed reads. For MQTT, monitor broker connection state as well as the last tag update.
  • S7, EtherNet/IP, Modbus, and BACnet use the device's poll_rate_ms. MQTT is event-driven and the simulator ticks at update_rate_ms. OPC UA additionally supports per-tag intervals through scan groups.
  • Set enabled = false to keep a device configured but disconnected — useful while commissioning.