# Migrating from legacy SCADA

Inventory the existing system, map its functions, and agree a cutover sequence. Start with one area, compare operation during a parallel run, and establish a fallback for each step.

## Catalog the legacy system.

### Points & devices

Every PLC/controller, its protocol, and the point list with types, scan rates, and addresses.

### Screens

Operator views and dashboards, plus which controls on them actually get used.

### History

Which points are historized, at what resolution, and what downstream reports consume them.

### Alarm logic

Setpoints, priorities, and how operators are notified today.

### SQL touchpoints

Recipe tables, production logs, reports — anything reading or writing a database.

### Users & roles

Who can see and write what, per area.

## Map each item to what ships today.

| Legacy item | Thermite SCADA surface |
| --- | --- |
| Device connections | Drivers: Modbus TCP, S7, EtherNet/IP, OPC UA, MQTT, BACnet/IP. DNP3, IEC 61850, and IEC 60870-5-104 are not integrated SCADA adapters. Confirm protocol coverage before a pilot. |
| Tag database / UDTs | Tag files (TOML). There are no UDT templates; organize definitions in files and folders. Your agent or a script can generate repetitive tag blocks for review. |
| Screens | HTML/CSS/JS screens with thermite.js live binding. Screens are rebuilt, not imported — there is no automated converter from any legacy format. |
| Historian | PostgreSQL-backed history with query-time aggregation, per-tag sampling and deadband. |
| Alarm annunciation | The alarm engine evaluates tag conditions, journals transitions, and exposes project alarm APIs. Notification pipelines support rosters, schedules, and escalation. Map existing conditions and notification rules; restart the gateway after changing alarm definitions or notification configuration. |
| SQL logging / recipes | Transaction groups (triggered inserts) and named queries. |
| Users & roles | With authentication enabled: per-project users, bindings, and role flags backed by local or gateway credential sources. LDAP/AD and SSO are not integrated. |

Identify functions that need coexistence or additional integration, then agree the migration scope and sequence. Review the [roadmap](https://thermitescada.com/product/roadmap) separately from available capabilities.

## Pilot → parallel → cutover → sunset.

### `01 · Pilot`

One line or cell. Enable authentication and use project roles without can_write_tags. Rebuild one operator screen, historize the required points, and verify driver behavior and data quality.

### `02 · Parallel`

Legacy stays authoritative. Thermite SCADA reads the same field data; compare values, history, and screen behavior side by side over real shifts.

### `03 · Cutover`

Per area: operators move to Thermite SCADA screens. With authentication enabled, grant write permission to the required roles. Retain the area's legacy screens as the agreed fallback.

### `04 · Sunset`

After every area cuts over and downstream reports read from the new historian, decommission legacy per site.

## Running both without crossed wires.

- Keep Thermite SCADA read-only during pilot and parallel — no field writes until an area formally cuts over.
- Confirm each device's session limits and polling load before adding a second client during the pilot.
- Where both systems speak MQTT, the broker is a clean shared read path.
- One project per area keeps cutover units independent — its screens, users, and publish lifecycle move together.
- Keep reviewed project source and configuration templates in Git. Revert and republish project changes; restore gateway settings through their reload or restart procedure. Keep live configuration and credentials in secured recovery backups.

## Scope it with us.

Bring the inventory from step 01 to a [technical session](https://thermitescada.com/contact) and we'll map it row by row, including functions that need coexistence or additional integration. Fixed-scope migration engagements are on [Services](https://thermitescada.com/services).